DESIGN NO. TRC/PV 120-18
VERTICAL (WALL), RATINGS: CAN/ULC-S115 2 HOUR (F, FH), 1 HOUR (FT, FTH); ANNULAR SPACING 1/16" MIN. & 3/16" MAX. - ABS, 6" PVC, ANNULAR SPACING 1/16" MIN. & 1/2" MAX. - 4" PVC, 3" CPVC
TEST PRESSURE DIFFERENTIAL - 50 Pa (0.20" OF WATER)

Manufacturer's Designation: Pipe Collar GW-21.
 


 

Wall: Minimum nominal 2 x 4 wood or steel stud framed gypsum wallboard faced wall assembly, providing a 2 hour rating.
Penetrations: Max. 4" diameter SCH 40 ABS or PVC DWN or process and supply, cellular core or solid, max. 3" diameter CPVC.
Metacaulk® Pipe Collar: Sized appropriately for pipe fastened to both sides of gypsum wall assembly in accordance with Rectorseal Corp. installation instructions.
Metacaulk® 1000: Optional - Sealant installed to a depth of 1/2".